Option H – Hart Serial Communications CP-10/CP-11
Features:
The Hart option board provides a Bell 202 interface to devices supporting the Hart protocol.
Each Hart option board can be used to communicate with up to 15 Hart devices. When communicating with a single Hart device (point to point installation), both analog and digital data can be read. When communicating with multiple Hart devices (multidrop installation) only digital data can be read.
Up to two Hart option boards can be installed on the one RTU allowing up to 2 point to point circuits or 2 multidrop circuits.
If using two separate point to point circuits and reading analog data, the RTU analog input channels must be isolated from each other.
Overview
- HART Protocol option board
- Communicates with up to 15 HART devices
- Fits CP-10, CP-11, CP-21, MC-11
Order Information
- COMMS-OPTION-H (Hart Interface (Limited functionality-refer to Product specifications) for CP-11/CP-21/MC-11, option port 2/3)
Datasheets
| Product specifications | |
| General | |
| Baudrate |
1200 Baud, ½ Duplex |
| Modulation | Bell 202 |
| Logical Frequencies | 1 = 1200 Hz 0 = 2200 Hz |
| Configuration Software | Toolbox |
| Internal Power Consumption | 1 mA from +5VDC Bus on backplane |
| Maximum No. Hart Devices | 15 (multidrop) |
| Data Available | Digital and analog for point to point Digital only for multidrop |
| Environmental | |
| Operating Temperature | -20°C to 70°C / -4°F to 158°F |
| Storage Temperature | -40°C to 85°C / -40°F to 185°F |
| Operating Humidity | 5 to 98% RH non-condensing |
Provides an interface to devices supporting the Hart protocol.