Option L – Line and Radio Interface FSK

Features:

The line option board provides a Private Line or Radio interface and is software configurable for either of these modes. There are two revisions of the line option board.

The original revision 'LINE-L' had a configurable output level (using Toolbox software). The newer revision 'LINE-2' has a fixed output level. Both have the same specifications.

Overview

  • Private/Line radio interface board
  • Fits CP-10, CP-11, CP-21, CP-30, MC-10, MC-11, LP-1

Order Information

  • COMMS-OPTION-L (2/4 Wire Line for CP-11/CP-21/MC-11, option port 2/3)

Datasheets

Product specifications:
General
Baudrate 1200 Baud
Modulation FSK, CCITT V.23
Carrier detect input Optical isolation
Active low or high
Min. input 2mA (70VDC max.)
RTS/PTT output

Microwave networks typically use a negative supply rail for the carrier detect circuit. The more positive rail should be connected to pin #6 (RTS/PTT) and the difference between the rails must not exceed 30VDC.
Optical isolation
Open collector output
Active low
30VDC max. at 20mA max.
Output impedance 30 K ohm
Input impedance 30 K ohm
Line termination 600 ohm
Line configuration 2 or 4 wire

The port is not full duplex and cannot use the full duplex functionality of a 4-wire configuration. 4-wire configurations eliminate the ability to communicate peer to peer but allow an increased number of drops on one link.
Line drive in multidrop configuration 10 drops for 2 wire
20 drops for 4 wire
Transmit output level -6 dBm (LINE-2)
-6 to -21 dBm software configurable (LINE-L)

Receive level
-43dBm to -9dBm

Transmission Distance
Allowing 3dB for background noise and a 10dB fade margin, up to 24dB of cable loss can be tolerated. Therefore, transmission distance = 24 / cable loss per Km (dB).

Note: if there are more than 2 RTUs (or other devices) on the line, reduce the allowable cable loss (24) by 1dB per additional RTU or device.
Configuration Software Toolbox
Internal Power Consumption 85 mA from +5VDC Bus on backplane
Isolation 3.88 kV
   
Environmental
Operating Temperature -20°C to 70°C / -4°F to 158°F
Storage Temperature -40°C to 85°C / -40°F to 185°F
Operating Humidity 5 to 98% RH non-condensing

T-box

Provides a private line or radio interface.