DI-5 Digital Input Dry Contact – 16-Channel I/O Module
Features:
The DI-5 provides 16 dry contact input points in one group with common power for field contacts. A wide range of input devices that are powered by the module can be used such as push buttons, limit switches and electronic proximity switches (these provide dry contact closures). Alternatively inputs can accept 10 to 28 Volts DC from an externally powered input.
Closure of the field contact results in a logic 1 in the status register.
The DI-5 counter module is similar to the DI-1, 16 channel digital input module (the DI-5 also has 16 digital inputs and can act like a DI-1). However, the DI-5 also counts pulses on the first 4 digital inputs. It is able to count up to 10kHz on inputs 1 and 2 and can count up to 255Hz on inputs 3 and 4. Inputs 5 to 16 are normal digital input channels. The pulse total and the pulse rate for each of the first 4 digital inputs are stored in internal registers.
This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane system.
Overview
- 16 Digital Inputs
- Pulse Counting on 4 Inputs
- Isolated DC Output For Powering Inputs
- 1kV Field to Logic Isolation
- Positive or Negative Polarity inputs
Order Information
- DI-5-1 (Digital Input - 16 channel (12-48VDC nominal Ch's 1&2 10kHz, Ch's 3&4 255Hz)
Datasheets
| Product specifications: | ||
| General | ||
| Output Power | 12VDC @ 80mA (1W) isolated, supplied by module | |
| Input Voltage Range | ±10 to 28 VDC (can use reverse polarity) Inputs per Module 16 |
|
| Isolation | 1000 Volts RMS between field and logic | |
| Contact Current | 4mA (typical) | |
| Input Characteristics: | ||
| On-state Current | 4.3mA minimum | |
| Off-state Current | 1mA maximum | |
| On response Time | Digital Inputs 1 and 2: 50µs maximum Digital Inputs 3 and 4: 500µs maximum Digital Inputs 5 to 16: 10ms maximum |
|
| Off response Time | Digital Inputs 1 and 2: 50µs maximum Digital Inputs 3 and 4: 500µs maximum Digital Inputs 5 to 16: 17ms maximum |
|
| Pulse Totalisation | Digital Inputs 1 to 4: 0-65535 Pulses | |
| Pulse Rates / Frequency | Digital Inputs 1 and 2: 10kHz maximum Digital Inputs 3 and 4: 255 Hz maximum |
|
| Environmental | ||
| Operating Temperature | -20°C to 70°C / -4°F to 158°F | |
| Storage Temperature | -40°C to 85°C / -40°F to 185°F | |
| Operating Humidity | 5 to 98% RH non-condensing | |
The unit provides 16 dry contact input points in one group with common power for field contacts.