DO-1 Isolated Relay Output NO/NC – 8-Channel I/O Module
Features:
The DO-1 provides 8 normally-open or normally closed relay circuits for controlling output loads. Output channels are isolated from the other channels and each pair of channels has a separate common terminal. The relay outputs can control a wide range of user-supplied load devices, such as: motor starters, solenoids and indicators. The user must supply the AC or DC power to operate the field devices connected to this module. Internal fuses protect the relay contacts should ratings be exceeded.
The insert in the hinged cover of the terminal strip has circuit wiring information. Circuit identification information can be recorded on the outside surface of the insert. The outside left edge of the insert is color-coded red to indicate a high-voltage module.
Overview
- 8 Relay Outputs NO/NC
- 3kV Coil to Contact Isolation
- 1 Common per 2 Channels
- 500V Channel Pair Isolation
- Can Switch AC or DC Voltages
Order Information
- DO-1-1 (Digital Output - 8 channel (N.O. & N.C. contacts)
Datasheets
| Product specifications: | ||
| General | ||
| Outputs per Module | 8 | |
| Commons | 4 (each common supplies 2 outputs) | |
Relay Type |
Omron G6B-2114P-US (datasheet is available from http://oeiweb.omron.com) |
|
| Rated Load (per contact) | 5A at 250VAC Resistive 5A at 30VDC Resistive (20A maximum per DO-1 module) |
|
| Maximum Operating Voltage | 380VAC, 125VDC | |
| Maximum Switching Power - Resistive | 1250VA, 150W | |
| Maximum Switching Power - Inductive | 375VA, 80W | |
| Minimum Load | 10mA at 5VDC | |
| Relay Operations | 100,000 minimum at 1800 operations per hour at rated load | |
| Relay Type | SPDT (Single Pole, Double Throw) | |
| Isolation | 3KV coil to contacts 500V between channel groups |
|
| Coil Rated Voltage | 12VDC @ 16.7mA | |
| Coil Resistance | 480 Ohm @ 12VDC | |
| Environmental | ||
| Operating Temperature | -20°C to 70°C / -4°F to 158°F | |
| Storage Temperature | -40°C to 85°C / -40°F to 185°F | |
| Operating Humidity | 5 to 98% RH non-condensing | |
The unit provides 8 normally-open or normally closed relay circuits for controlling output loads.