IO-5 Combination Analog Digital I/O Module – 8 Input/5 Output

Features:

The combination analog/digital I/O module provides:

  • 4 x AI Analog inputs
  • 1 x AO Analog output
  • 4 x DI Digital input / 10 KHz counters
  • 4 x DO Digital outputs (solid state sinking)

Analog I/O

This module provides two signal ranges, 0 to 20mA and 4 to 20mA. The default range is 4-20mA. A link on the rear of the module selects 4-20mA (link installed) or 0-20mA I/O for all channels.

This module provides two signal ranges, 0 to 20mA and 4 to 20mA. The default range is 4-20mA. A link on the rear of the module selects 4-20mA (link installed) or 0-20mA I/O for all channels.

Resolution of the converted signals is 12 bits binary (1 part in 4096). The sign bit is not used in the conversion process. All channels are updated four times per second.

All inputs share a single common and all outputs share a separate common at the zero volt rail.

Input protection for the module is sufficient to guarantee operation with reduced performance with up to 1500V common-mode. The module provides electrical isolation of externally generated noise between field wiring and the backplane through the use of optical isolation.

Digital I/O

Input characteristics are compatible with a wide range of user supplied input devices, such as push buttons, limit switches and electronic proximity switches, while outputs can control a wide range of user supplied load devices such as: motor starters, solenoids and indicators.

All four Digital Inputs share one common rail. All channels can be configured as pulse counters that appear as 16-bit unsigned integer values in the analog input registers of the RTU processor module. Because of processor module limitations, only channels 1 and 2 can be configured as pulse counters when used with the CP-11 and PC-1 processors (Toolbox32). All four channels can be used as pulse counters when used with CP-30 processor module (Toolbox PLUS+).

Four isolated Digital Outputs are provided on the module. All four Digital Outputs share one common rail. Solid state output switches are protected from over-currents and shorts and also from overheating. Digital Outputs can control a wide range of loads such as: motor starters, solenoids, indicators, etc. The user must supply the DC power to operate field devices.

Overview

  • 4 Digital Inputs / 10 KHz counters
  • 4 Digital Outputs (solid state sinking)
  • 4 Analog Inputs
  • 1 Analog Output

Order Information

  • IO-5-1 (Multi I/O 4xDI + 4xDO + 4xAI + 1xAO)

Datasheets

Product specifications:
Analog Input Section
Input Current Ranges 4 to 20mA and 0 to 20mA
Input Voltage Ranges * 1 to 5V and 0 to 5V *
Calibration Factory calibrated to 5µA
Update Rate 2 msec (all four channels)
Absolute Accuracy 0.1% full scale + 0.1% reading
Resolution 12 bit (no sign bit)
Common Mode Voltage 1500 Volts
Linearity <1 Least Significant Bit
Isolation 1000 Volts RMS between field and logic
Common Mode Rejection >70 dB at DC; >70 dB at 60 Hz
Cross-Channel Rejection >80 dB from DC to 1 kHz
Input Impedance 250 ohms (100 ohms optional)
Input Filter Response 325 Hz
   
* Analog inputs can be modified from current inputs to voltage inputs by lifting one leg of the 250 ohm channel resistor. Each channel has its own resistor, so any combination of channels can be converted.
 
Analog Output Section
Output Current Range 4 to 20mA and 0 to 20mA
Calibration Factory calibrated to 68µA per count
Supply Voltage (nominal) +5V and +12VDC from backplane
Update Rate 250 msec (all channels) Determined by I/O scan time, and is application dependent
Absolute Accuracy 0.1% full scale
Resolution 12 bit (no sign bit)
User Load 0 to 850 ohms
Output Load Capacitance 2000 pF
Output Load Inductance 1H
Isolation 1000 Volts RMS between field and logic
 
Digital Input Section
Rated Voltage 30 Volts DC
Maximum Counters Speed 10 KHz
Inputs per Module 4
Isolation Transient voltage: 3 KV
Input Current Approx. (Vin / 4.7) mA: 2 mA @ 9.4 V in; 6.4 mA @ 30 V in
Input Characteristics:  
On-state Voltage 10 VDC minimum
Off-state Voltage 4.0 VDC maximum
   
Digital Output Section
Maximum Switched Voltage 30 VDC
Maximum Switched Current 2 A per channel
Outputs per Module 4
Isolation Transient voltage: 3 KV
Output Type Optically isolated, solid state, sinking
 
Environmental
Operating Temperature -20°C to 70°C / -4°F to 158°F
Storage Temperature -40°C to 85°C / -40°F to 185°F
Operating Humidity 5 to 95% RH non-condensing
Maximum working voltage on any contact to the field connector 42.4 Vpeak / 60 VDC relative to system (backplane) ground
T-box