RIM Remote Input Module
Remote I/O features:
The RIM module is designed to monitor and report the status of it's 4 digital inputs for a remote alarm and/or location application. This Remote I/O module has 3 inbuilt RS232/485 serial ports and custom firmware can be developed to give it further functionality or allow it to support other protocols such as MODBUS. The RIM has been designed to allow it to perform varied monitoring and reporting applications in any industry.
It has a wide operating voltage of 9-32 Volts DC and the 4 inputs are monitored for integrity. The rugged case is waterproof and is rated to IP67.
If you have a requirement for remote monitoring and reporting, the RIM module could be the answer. For more information on the RIM module or any other of our product development platforms, please send an email to info@rtunet.com
Remote I/O applications:
- Level monitoring
- Alarm Status Reporting
- Vehicle Tracking and Status
- Security Monitoring
- Event Counting and Recording
- Gate Position Monitoring and many more...
| Remote I/O product specifications: | |
| Digital Specification | |
| Input Voltage Range | 9.5 to 32 Volts DC |
| Isolation | 100 Volts RMS between field side and logic side |
| Contact Current | 4mA typical |
| Input Characteristics | |
| On-state Current | 4.0mA minimum |
| Off-state Current | 1.0mA maximum |
| On Response Time | Digital inputs 500us maximum |
| Off Response Time | Digital inputs 500us maximum |
| Continuity Detection | All 4 channels, provided 4K7 resistor fitted across contacts. (Device end) |
| Operating Temperature Range | -20°C to 70°C |
| Storage Temperature Range | -40°C to 85°C |
| Operating Humidity | 5 to 95% non-condensing |
| CPU Board Specification | |
| Main CPU | H8 2144 |
| Onboard Flash | 128KB |
| Frequency | 7.3828 MHz |
| Real Time Clock | ±60 sec/month, without GPS sync. GPS time syncing can be used for enhanced accuracy. |
| Communication Specification | |
| Port 1 | RS232 wih RTS, CTS (Remote Modem Port. Eg Radio, GSM, CDMA, Satellite, etc) Max 57600 Baud, 9600 nominal |
| Port 2 | RS232 no hardware handshake Max 57600 Baud, 9600 nominal |
| Port 3 | RS232 no hardware handshake Max 57600 Baud, 9600 nominal |
The Remote I /O module is designed to monitor and report the status of its four digital inputs for a remote alarm and/or location application.